10/06/2022April Daniels
Symptom "Disable Web Server" checkmark is missing on the LNL-2220 Configuration Web Page. Resolution In order to access the Configuration Web Page, DIP Switch 1 on the LNL-2220 must be in the ON position. If DIP Switch 1 is in the OFF ...
10/06/2022April Daniels
Symptom "Day Contact Restore" alarms come into Alarm Monitoring on NGP panels Resolution This was found because the EOL configuration for the REX input was wired incorrectly. Refer to the NGP Hardware Installation Guide for more informa...
10/06/2022April Daniels
Symptom NGP PANELS KEEP FLUCTUATING ON AND OFFLINE Resolution GO INTO THE ACS.INI FILE ON THE MACHINE RUNNING THE LS COMMUNICATION SERVER AND CHANGE THESE SETTINGS IN THE SERVICE SECTION CHANGE MAXPANELSPERTHREAD FROM 8 TO 1 [Service...
10/06/2022April Daniels
Symptom While trying to print from the Fargo HDP5000 Printer, the following error message appears: Error 28 No Film . Resolution This error appears when either the ribbon cartridge or the HDP film cartridge is not installed. To ...
10/06/2022April Daniels
Symptom After downgrading LNL-2210, LNL-2220, or LNL-3300 firmware from 1.173 to 1.143, the panel does not come online. Resolution If the panel does not come online after downgrading the firmware, take the following steps: Remove p...
10/06/2022April Daniels
Question Is the Schlage PIM-400-485-SBB supported in OnGuard?
Answer
The Schlage PIM-400-485-SBB is not supported in OnGuard.
The Schlage PIM-400-485-RSI is supported in OnGuard.
Both devices look exactly the same. To i...
10/06/2022April Daniels
How to change the keypad output mode on Schlage AD300/AD400 locks to 8-bit. Procedure Steps Connect the HHD/SUS to the AD-300/400 using the HHD USB cable. The connector on the AD-300/400 is on the bottom of the outside escutcheon (reader/keyp...
10/06/2022April Daniels
Question Why can't I import cardholder data using a Scanshell 1000N or 1000N-A?
Answer
The ScanShell 1000N and ScanShell 1000N-A are not compatible with OnGuard applications. The 'N' in the model number indicates that the hardwar...
10/06/2022April Daniels
Symptom Alarms that are generated on the NGP panel are not transmitted to the HSC-IP Central Station receiver. Resolution Ensure that Port 443 is open and is not blocked (this may require contacting the IT department). If the port is c...
10/06/2022April Daniels
How to wire a L1 4G reader for enrollment over RS-232 instead of USB Procedure Steps 1. For RS-232 installations, a female DB9 connector should be used on the cable.
2. Connect RS232_TX (Violet wire - Pin 4 of 28) to the DB9 - Pin 2.
3. Conne...