								 Question      How do I upgrade from Secure Perfect 6.1.1 to FCWnx 7.7?   Answer      When upgrading from Secure Perfect 6.1.1 to any version of FCWnx, ensure that Service Packs 2 and 3 were applied to the souce database before the conversion.    IMP...							
						 
											
														
							
								10/06/2022April Daniels
																	
							
							
								 Symptom           CHECKSUM error is appearing in Diag View for FCWnx and micro is experiencing various issues.    Resolution        The check needs to be reimaged (NOT REFLASHED!). In most cases, this would require the tech to send the SIMM in for u...							
						 
											
														
							
								10/06/2022April Daniels
																	
							
							
								 Symptom       Customers have noticed an increase in the rate of failure to update via the Flash Process with R124  firmware and higher. This process change will impact upgrading PXNplus/DirecDoor/ACUXLplus  controllers to R124 firmware or higher.   ...							
						 
											
														
							
								10/06/2022April Daniels
																	
							
							
								 Symptom      When attempting to install FCWnx, the following error message appears: 
   There is a problem with this Windows installer package. A program required for this install to complete could not be run. Contact your support personnel or pack...							
						 
											
														
							
								10/06/2022April Daniels
																	
							
							
								 Symptom       If an unknown error occurs while trying to connect to the database when licensing a client, and you can ping the server and access shared folders, use the following steps.    Resolution       Go to  Program Files > GE > FCWnx > Logs > ...							
						 
											
														
							
								10/06/2022April Daniels
																	
							
							
								 Product Name      FCWnx   General Information      SQL PORT DERIVED FROM SERVER   135 client\server comm port (RPC)    1024-1028   6699 controller comm port   6700-6715 application   8085 start video comm port   8088 server video stream   8089 start...							
						 
											
														
							
								10/06/2022April Daniels
																	
							
							
								 Restoring Databases Through SQL   Procedure Steps       
  Stop all FCWnx services.  Open  SQL Server Management Studio  and expand the  Databases  folder.  Right-click on the database you want to restore.  Go to  Tasks > Restore , and click on  Da...							
						 
											
														
							
								10/06/2022April Daniels
																	
							
							
								 Symptom      The SecurePerfectHistory database is not archiving.   Resolution       Manually Archive Secure Perfect History database (KB article 3234).  Backup Secure Perfect and Secure Perfect Archive databases.  Run CreateDB.  Restor SecurePerfect...							
						 
											
														
							
								10/06/2022April Daniels
																	
							
							
								 Symptom      IDispatch 3092 error   Resolution      Open SQL Server Management Studio.  Right-click on the instance (SERVER\SPSQL) and select  Properties .  Under  Select a page , select  Memory .  Set the  Maximum server memory  to 1/2 the physical...							
						 
											
														
							
								10/06/2022April Daniels
																	
							
							
								 Manually archiving through SQL when the Database Maintenance Utility is not working, or when you would prefer to archive through SQL.   Procedure Steps      Log into SQL Server Management Studio.  Expand  Databases .  Expand the  SecurePerfectHistor...