Symptom
If a custom Open Line Event alarm is required from a door contact or REX input, the default Alarm Definitions device list will not display the individual reader inputs.
Resolution
To enable the reader inputs in the device list:
- Add the following to the acs.ini file:
- [SystemAdministration]
- AlarmDefIncludeDCRex=1
- Restart Comm Server and Reopen System Admin.
- In System Administration, go to Monitoring > Alarms > Alarm Definitions and do the following:
- Add a new definition.
- Enter a name for the new definition.
- In the Hardware list, you will now see Door Contacts. Select the Door Contact for the reader.
- Select Open Line Alarm Active for the event.
- Assign it over to the right.
- Click [OK]
- Refresh your alarm configuration, or restart Alarm Monitoring.
- You should see the custom alarm for the door contact.
Applies To
OnGuard (All versions)
Additional Information
Copyright © 2022 Carrier. All rights reserved.