Symptom
If an LDVR is disconnected from an OnGuard system for an extended period of time, communication errors that have not been processed by the Communication Server may be generated and saved on the LDVR.
When connected, the LDVR slowly releases these errors, as many as 10,000 or more, depending on how long the LDVR was disconnected.
The error messages appear as alarms in Alarm Monitoring.
When connected, the LDVR slowly releases these errors, as many as 10,000 or more, depending on how long the LDVR was disconnected.
The error messages appear as alarms in Alarm Monitoring.
Resolution
When the LDVR services are stopped, the LDVR queues up alarms and releases them at a controlled rate. If necessary, this message queue can be deleted.
To delete the message queue:
- Using the installed batch file, stop all LDVR services.
- Delete the file LocalServer.sel, located on the LDVR at either C:\WINDOWS\system32 or C:\WINNT\system32.
- Restart the LDVR services.
- Repeat Steps 1-3 until the size of the LocalServer.sel file reaches 0 KB.
LDVR (All versions)