Symptom
Global I/O's have stopped firing but a 'Global Linkage Action Failed' alarm does not show up in Alarm Monitoring. The Global I/O's can be started up again by simply restarting the Communication Server.
If you see this occurring but also observe the following logs
In Windows Event Viewer, the system logs shows the following error:
Log Name: System
Source: Microsoft-Windows-Kernel-General
Date:
Event ID: 1
Task Category: None
Level: Information
Keywords: Time
User: LOCAL SERVICE
Computer: Hostname
Description:
The system time has changed to ?2013?-?01?-?23T21:39:46.857000000Z from ?2013?-?01?-?23T21:39:46.857847700Z.
In the LenelError log you may find this entry:
TIME: [x/xx/2013 12:21:38 PM]
SEVERITY: Error
ERROR CODE: 0x20010001
PROGRAM: LSLServer
FILE: ACSEVPRT.CPP (LINE 1410)
DETAILS: Internal logic error.: Timeout hit for no data over socket from Communication Server "SERVERNAME". There have been 1 such errors since the last log entry
TIME: [x/xx/2013 12:21:38 PM]
SEVERITY: Error
ERROR CODE: 0x20010001
PROGRAM: LSLServer
FILE: ACSEVPRT.CPP (LINE 1410)
DETAILS: Internal logic error.: Timeout hit for no data over socket from Communication Server "SERVERNAME". There have been 1 such errors since the last log entry
Resolution
This resolution was found on a Virtual Server VMWare ESXi in the VMWare tools there was a setting for "time sync", deselect this option
Applies To
OnGuard (All versions)