Symptom
Alarm events from Bosch GV2 and GV3 panels are delayed coming into OnGuard.
Resolution
There is a new setting in the Bosch GV2 and GV3 point index for "Alarm Abort". This must be set to "NO" for OnGuard to receive the alarms without any delay.
Applies To
Third Party Hardware